Based on the CIBSE CP1 2020 / Danish Code of Practice DS 439
Link
https://www.cibse.org/knowledge/knowledge-items/detail?id=a0q3Y00000IMrmGQAT
Application
Domestic Hot Water
This standard calculates the diversity based on
Since the standard does not provide
design flows for individual tapping points
or a formula to apply diversity on the total DHW flow within one dwelling
it is not possible to define tapping points using this standard,
you must specify and lock the diversified flow of each HIU manually.
Diversity formula
With this calculation method, the diversity factor decreases according to the formula (2qm + Θ(Σqf-2qm) + Asqrt(qm*Θ)sqrt(Σqf-2qm))/Σqf, in which Σqf = T = the sum of the diversified HIU flows.
This formula only applies when 0.2 <= T. It is important to note that calculation is applicable for T expressed in liter per seconds. We assume A=3.1; Θ = 0.015; qm=0.1
Applies diversity
Requires recalculation of DHW flows?
No.