Pump found in variable part of dividing circuit
Pump found in variable part of dividing circuit
The error message
This error shows if there is a pump placed after a dividing circuit, as this arrangement does not allow for the needed mixing that the valve is supposed to do. The pump should be placed before the diving circuit.