Error/warning overview

Error/warning overview

  1. System Check (SYS)

    1. Errors (ESYS)

    2. Warnings (WSYS)

  2. Compute design flow (PRO)

    1. Errors (EPRO)

    2. Warnings (WPRO)

  3. Pipe selection (PIP)

    1. Errors (EPIP)

    2. Warnings (WPIP)

  4. Optimise system components (OPT)

    1. Errors (EOPT)

    2. Warnings (WOPT)

  5. Simulation (SIM)

    1. Errors (ESIM)

    2. Warnings (WSIM)


System Check (SYS)

Errors (ESYS)

ESYS0001

The error message

Meaning

This error shows the fact that there is no pump placed to provide the necessary flow to the production unit/end unit/valves.

This can happen with a multitude of different components. The errors are as follows:

  • No pump for

    • Gate X of this buffer

    • the ventilation cooling unit

    • this changeover on the cooling/heating side

    • this end unit

    • this production unit

  • No pump in recirculation circuit

  • No pump on primary side of mixing circuit

  • No pump on secondary side of the second heat exchanger

  • No pumps over this control valve

  • Pump missing on

    • Primary/secondary side of heat exchanger

    • Primary/secondary side of heat pump booster

    • Primary/secondary side of the hydraulic separator

ESYS0002

The error message

This error allows you to keep calculating but is an hydraulic error.

Meaning:

There are 2 pumps which are placed in ‘series’. The error shows up because the second pump is placed after a mixing valve. When the valve is fully open the pumps are in series. Pumps in series cause control interference between the pump controls and the three-way valve controls, causing faster degradation of the three-way valve together with reduced control performance in operation.

How to solve:

You can solve this error in multiple ways:

  1. Remove the primary pump and rely on an active distribution circuit.

  2. Replace the active distribution circuit to a passive distribution circuit.

More information on active/passive distribution circuits can be found here: https://hysopt.atlassian.net/wiki/x/4YUhu

It is possible that during renovations, the erroneous situation is effectively in place. Therefore, you can continue working with the error to reproduce the behaviour in simulation. However, it is discouraged strongly to have pumps in series in your designs.

ESYS0003

The error message

Meaning

This error message shows during the system check if a base circuit (a block) is orientated incorrectly.

In the example above, you can see a pump in the supply line that is directed away from the end unit. Thi pump is thus installed in the wrong flow direction (note the arrows shown on the heat exchanger), hence the pump should be flipped (use shortcut 'F') and reconnect the pipes.

How to solve

Ensure that the highlighted base circuit is currently oriented. Use the shortcut ‘F' to flip the base circuit and the shortcut 'r’ to rotate the base circuit. The expected orientation is governed by following rules:

  • Pumps in the supply line should be directed towards end units.

  • Pumps in the return line should be directed towards production units.

  • On all other base circuits, the expected orientation is always displayed with an arrow.

ESYS0004

The error message

Meaning

This error shows if there is a pump placed after a dividing circuit, as this arrangement does not allow for the needed mixing that the valve is supposed to do.

How to solve

The pump should be placed before the diving circuit.

ESYS0005

The error message:

Meaning

This error message shows that there is a pump missing between the boiler and hydraulic separator.

How to solve

Place a pump at the primary side of the hydraulic separator.

Warnings (WSYS)


Compute Design Flow (Pro)

Errors (EPRO)

Error EPRO0001: Supply temperature mismatch

Error EPRO0002: Could not resolve power propagation for this node

Error EPRO0003: UA Value and primary return/air volume flow are both locked

Error EPRO0004: Illegal combined power parameter state

Error EPRO0005: Different applications conjoined at this point

Error EPRO0006: Both supply and return temperatures are overridden

Warnings (WPRO)

Currently empty


Pipe selection (PIP)

Errors (EPIP)

Currently empty

Warnings (WPIP)

Currently empty


Optimise system components (OPT)

Errors (EOPT)

EOPT0001: KVs value set to zero

EOPT0002: Fixed pressure drop lower than minimal required pressure drop

EOPT0003 : Pump head …m/…kPa not enought for loop pressure loss …kPa

EOPT0004: Total pressure drop larger than 20 bar

EOPT0005: No pumps provide pressure for this control valve

EOPT0006: Both pump head and pump curve are locked

EOPT0007: Design volume flow rate out of range of pump curve

EOPT0008: Override supply temperature and secondary supply temperature are too close together

EOPT0009: No suitable KVS-value found

EOPT0010: No suitable valve position can achieve the desired mixing ratio

EOPT0011: Short circuit on premix bypass

EOPT0012: Control valve heas pump downstream

EOPT0013: No pumps expected

Warnings (WOPT)

WOPT0001: Authority lower than minimal required authority


Simulation (SIM)

Errors (ESIM)

Error ESIM0001: Failed to parse code/expressions

Error ESIM0002: The volume of the zone is zero

Error ESIM0003: Invalid column name in CSV file

Error ESIM0004: Heat pump safety: Condenser temperature above 100°C

Error ESIM0005: Hydraulic system solver failed Time in simulation …h

Warnings (WSIM)

Warning WSIM0001: Total losses through windows are larger than design heat load