Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Link

https://www.cibse.org/knowledge/knowledge-items/detail?id=a0q200000090MYHAA2

Application

Domestic Hot Water

This standard calculates the diversity based on

  • Number of tapping points
  • Type of the tapping points
  • Total DHW flow
  • Diversified DHW flow
  • Number of dwellings

Diversity formula

With this calculation method, the diversity factor decreases according to the formula (1.19 * N + 18.8 * N^0.5 + 17.6) / (37.5*N), in which N is the number of dwellings.

The diversified flow rate for one dwelling is calculated based on the default power 37,5 kW as mentioned in the DS 439 (CIBSE CP1 2015).

Variant for high DHW usage

We also support the variant for high DHW usage. With this calculation method, the diversity factor decreases according to the formula (0.0417 + 0.015 * (0.0555N-0.0417) + 0.0775 * sqrt(0.0555N-0.0417)) / N*0.0555), in which N is the number of dwellings. The concurrent flow rate for one dwelling is calculated based on the default power 38 kW as mentioned in the F:101.

Applies diversity

  • inside the dwelling
  • outside the dwelling

Requires recalculation of DHW flows?

No.

  • No labels