Connector of tee fitting is not connected (disconnects)
In case of a disconnect, the BIM syncer will handle it as a fitting with two connectors, so it will not handle it as a Tee-point.
Cap open end of tee fitting
Pipe is connected to tee fitting which is capped with a pipe cap
Tee fitting is connected with a pipe cap
BIM Syncer will handle that branch as a dead-end branch, and it will handle the fitting (from a hydraulic perspective) as a fitting with two connectors, so it will not handle it as a Tee-point.
A non-capped pipe is connected
If a non-capped pipe is connected, then the BIM Syncer will handle it as a fitting with three connectors. It is assumed that this pipe is not fully modelled and needs additional pipe segments, fittings, and components.