Hysopt BIM Syncer can create a P&ID model (calculation model) from a Revit model. It uses a smart algorithm that first identifies the end units (heat emitters) in your system, such as radiators, fan coils, or floor heating. Then, it analyses how the system is connected with components and pipes, such as pumps, valves, or fittings. The algorithm stops when it reaches a production unit, such as a boiler, chiller, or heat pump. This way, Hysopt BIM Syncer can generate a complete and accurate P&ID model of your system.
...
System check (pump placeholders needs to be present or component placeholder should be replaced by a pump base circuit)
Compute design flows and select pipes (regime changing component placeholders must be replaced)
Header configurations (bypass on the header)
Piping system
In the Hysopt BIM Syncer we know several applications :
heating
cooling
By default, the Hysopt BIM Syncer will take a look at the endunits, and based on the available info on that endunits, generate a model with the corresponding application. If no further information is available, it will generate by default a heating application.focus on heating and cooling applications while Revit piping systems are used for serveral other applications eg. domestic cold and hot water, fire protection, sanitary. Heating and cooling applications in Revit use the same piping system classification hydronic supply and hydronic return. Hysopt BIM Sycner cannot differ heating or cooling system based on piping system classifications in Revit. For this reason an assistance parameter is added to inform the Hysopt BIM Syncer if a hydronic system is a heating or cooling system. At default all hydronic systems will be generated as heating systems
Hysopt model generation settings https://hysopt.atlassian.net/wiki/spaces/HBF/pages/3341320351/Settings#Hysopt-model-generation
...
Unprocessed mixing/dividing point in the system. Maybe you need to mark some components as endunit on these branches
...
We found a branch with an unknown location," this might indicate that the classification type of the pipe segments is not consistent in our BIM model
This point in the system has {number} pair of branches, this is not supported yet by the generator
Errors
No end units found
...
Successful Hysopt model generation
...