Application

Domestic Hot Water

This standard calculates the diversity based on

  • Number of tapping points
  • Type of the tapping points
  • Total DHW flow
  • Diversified DHW flow
  • Number of dwellings

Since the standard does not provide

  • design flows for individual tapping points

  • or a formula to apply diversity on the total DHW flow within one dwelling

it is not possible to define tapping points using this standard,
you must specify and lock the diversified flow of each HIU manually.

Diversity formula

With this calculation method, the diversity factor decreases according to the formula (2qm + Θ(Σqf-2qm) + Asqrt(qm*Θ)sqrt(Σqf-2qm))/Σqf, in which Σqf = T = the sum of the diversified HIU flows.

This formula only applies when 0.2 <= T. It is important to note that calculation is applicable for T expressed in liter per seconds. We assume A=3.1; Θ = 0.015; qm=0.1

Applies diversity

  • inside the dwelling
  • outside the dwelling

Requires recalculation of DHW flows?

No.