The exports in Hysopt are all linked to a specific part namely designer, calculator and simulator 

The following exports are available in Hysopt:

Before you start exporting, it is useful to label all the necessary components. This will make the following part of the process significantly easier.

Labels are added through the layer "Text", the label is only connected to the base circuit if it is within following radius (see picture below). When there are 2 base circuits near a label it will take the closest one.

Designer

Export model to PDF

When exporting your model to a PDF, a screenshot is taken of the model. Than you can chose on which papertype (A0 - A4) and which DPI (Dots Per Inch) the model must be generated.

Calculator (after optimize pumps and valves)

Get component list

In the component list, all the components from base circuits that are drawn inside the model are listed by type and amount.

New Wiki - Installation report

In the installation report, all the information is listed by the type of base circuit. 

The installation report is intended for installation and commissioning, by labeling all of the base circuits the exported list (Excel) will be linked to the scheme. So for each label all of the calculated parameters are shown per base circuit (see example below).

For Example: Circuit A shows following calculated parameters

  • Pump: pump head and volume flow

    Three-way control valve: Kvs-value and actual authority

    Balance valve on bypass: Kv-value

    Balance valve for pump: Kv-value, preset and volume flow

    Pipe size

In the figure below you can see an example from a installation report. 

Pump selection report

This report describes the most critical path for each pump individually.

In the figure below you can see an example from a pump selection report

Simulator

Get energy report

After a simulation you can download an energy report of your model. In this report, the energy consumption of productions and pumps can be found as well as the indication of comfort in the zones and in domestic hot water productions (satellite unit).