https://www.eyrolles.com/BTP/Livre/dtu-60-11-regles-calcul-des-installations-de-plomberie-sanitaire-et-des-installations-d-evacuation-des-eaux-pluviales-0000000461115/

Application

Domestic Hot Water

This standard calculates the diversity based on

  • Number of tapping points
  • Type of the tapping points
  • Total DHW flow
  • Diversified DHW flow
  • Number of dwellings

Diversity formula

With this calculation method, the diversity factor decreases according to the diversity factors as defined in the standard. For more than 1 dwelling, it decreases according to the formula 0,8 / square root (N -1), in which N is the number of dwellings.

WARNING : when using this method, you will have to define and lock the diversified hot water flow rate for an individual dwelling yourself in the DHW regime on each individual HIU or ILS building block. For HIU's without a locked diverisifed flow rate, a default value of 0.6 m3/h will be used.

Applies diversity

  • inside the dwelling
  • outside the dwelling

Requires recalculation of DHW flows?

No.