Introduction

Domestic hot water flow rates have always been challeging to calculate, because we need to take into account the simultaneous usage of hot water tapping points. Not all tapping points (like showers) will be use at the same time, so a so we need to take into account in each part of the system, the maximum probability, or the maximum DHW flow of simultaneous tapping points. These are defined in diversity standards. Most of these methods only account for simultaneous flow rates, and not for simultaneous power, because domestic hot water networks are mostly operated as single pipe / fixed temperature systems.

When carrying over these norms to the central heating system (HIU’s, heat exchangers, storage tanks, ….), the propagation and aggregation of diversity becomes very important! This effect is amplified by the fact that central heating often operates at lower power but higher flow rates / smaller temperature delta and domestic hot water heat exchangers operate at higher power but lower flow rates.

Hysopt incorporates diversity for DHW (DIN 1988-300, Cibse CP1, Danisdh Code of Practice 439, Swedish regulation DHA F:101, French Costic MTA 2016, French DTU 60-11, …) and diversity for central heating (Cibse CP1.2, logarithmic, …).
We have extended the calculation to cope with simultaneous central heating and domestic hot water usage, and with combination of power needed in mixed systems.

Overview

To explain diversity and aggregation, we use following example model of 2 HIU’s.

First of all, we make a distinction between the calculations within one dwelling, and the calculations over multiple dwellings.

Example (outdated)

Consider a system of appartments, each having a satellite heat exchanger for instantaneous domestic hot water production. To keep the example simple, we assume each appartment to have a DHW heat load of 40kW with a temperature regime of 70°C / 30°C, and a 15kW central heating heat load, with a temperature regime of 70°C / 60°C. This results in following flow rates in relation to n. We use M for total mass flow.


Q CH (kW)

M CH (kg/s)

Q DHW (kW)

M DHW (kg/s)

1

15

0.36

40

0.24

2

30

0.72

80

0.48

3

45

1.08

120

0.72

4

60

1.43

160

0.96

5

75

1.79

200

1.19

6

90

2.15

240

1.43

7

105

2.51

280

1.67

8

120

2.87

320

1.91

9

135

3.23

360

2.15

10

150

3.58

400

2.39

Because all domestic hot water (DHW) units will never be active at the same point in time, we use a simultaneous flow rate for DHW, using the following formula:

m = a * M^b + c

with a = ..., b = ... and c = ...

Hysopt then computes a simulateous factor f = m_DHW/M_DHW. We then compensate for the central heating volume flow and power on units not in DHW mode, by computing the combined mass flow

m = f * M_DHW + (1-f) * M_CH

Simply taking the maximum of M_CH and f * M_DHW  would result in a flow rate which is too low. For component selection and pipe sizing, the maximum of m and M_CH is used.

To give an indication of the regime and power associated with these simulataneous flow rates, we compute

Q = f * Q_DHW + (1-f) * Q_CH and Q sizing = MAX(Q_CH, Q)



Q CH (kW)

M CH (kg/s)

Q DHW (kW)

M DHW (kg/s)

m DHW (kg/s)

f (-)

m total (kg/s)

Q total (kW)

m sizing (kg/s)

Q sizing (kW)

T return (°C)

1

15

0.36

40

0.24

0.17

0.72

0.27

33

0.36

33

48.0

2

30

0.72

80

0.48

0.33

0.69

0.55

64

0.72

64

48.5

3

45

1.08

120

0.72

0.43

0.60

0.86

90

1.08

90

50.0

4

60

1.43

160

0.96

0.51

0.53

1.18

113

1.43

113

51.1

5

75

1.79

200

1.19

0.57

0.48

1.51

135

1.79

135

52.0

6

90

2.15

240

1.43

0.62

0.43

1.84

155

2.15

155

52.8

7

105

2.51

280

1.67

0.67

0.40

2.17

175

2.51

175

53.3

8

120

2.87

320

1.91

0.71

0.37

2.51

194

2.87

194

53.8

9

135

3.23

360

2.15

0.75

0.35

2.85

213

3.23

213

54.2

10

150

3.58

400

2.39

0.78

0.33

3.19

232

3.58

232

54.5


Graphs (outdated)

To clarify things further, we include some graphs for the combined flow rates and power. These graphs are for increasing domestic hot water power / flow rates at 70° / 30°C with a fixed power of 50kW heating at 70° / 60°C.