...
This standard calculates the diversity based on
- Number of tapping points
- Type of the tapping points
- Total DHW flow
- Diversified DHW flow
- Number of dwellings
...
Yes. This standard assumes a DHW regime of 15°C for cold water and 60°C for hot water, resulting in a mixed temperature of 37,5°C (when both flows are equals). If the temperatures in the Hysopt model deviate from this standard regime, the design flows for cold and hot water are first recalculated (in order to achieve a mixed design flow of 37,5°C), see Step 1 : recalculation of the tapflows for more info.
Remarks
For appartments apartments with low volume flows, there is a small “strange“ bump in the diversity graph if you apply the formula
...