DHW flow 1, with total power P1, diversity flow v1, and diversity factor f1
DHW flow 2, with total power P2, diversity flow v2, and diversity factor f2
...
The question is : how to calculate the diversity factor f3, total power P3 and diversity flow v3 for DHW?
P3 = P1 + P2 (first law of thermodynamics)
f3 is recalculated based on the applicable diversity standard, applied on the TOTAL amount of tapflow or TOTAL amount of dwellings on the secondary side.
the supply temperature t3supply is defined by the user
the return temperature t3return is calculated as the mixed return temperature (v3 * t3return = v1 * t1return + v2 * t2return)