Introduction
To avoid pipe oversizing, Hysopt will aggregate and weigh the different heating applications in the network. On each pipe, the supply for
...
are aggregated and weighted based on diversity factors.
...
Aggregation methods
Design flow rates for heating prioritised by DHW, heating not prioritised by DHW, and DHW in the common pipe sections are calculated separately.
To calculate the installation components (pipe sections, primary pump, storage tank, boiler, ...) it is however necessary to have one design flow rate and one thermal power. Therefor Hysopt has developed two methods to aggregate the flow rates and thermal power in the common pipes as explained below.
...
In the tab “Domestic Hot Water Design Flows“, you can select one of the following two “primary flow rate aggregation methods”.
Maximum of central heating and simultaneous hot water flow
Weighted average of central heating and total domestic hot water flow
...
Maximum of central heating and simultaneous hot water flow
In the graph below, the design flow rate of DHW and CH is shown as a function of the number of apartments. The CH flow rate, logically increases linearly as the number of apartments increases (blue solid line). The DHW flow rate increases non-linearly, as a consequence, the DHW flow rate at the upper apartments will be determining the flow rate, as the number of apartments increases the CH flow rate takes over. The maximum of both will be used for component calculation (pipe sections, primary pump, storage tank, boiler, ...). The design flow rates, thermal power and temperature regimes (CH and DHW) are shown on the labels below.
...
Weighted average of central heating and total domestic hot water flow
In the second method the weighted average of central heating and total domestic hot water flow is taken into account. In contrast to the first method this method takes into account that some of the satellite units use DHW simultaneous and others will use CH. Simply taking the maximum of CH and DHW flow rate would result in some cases a flow rate which is too low. Hysopt uses the simultaneous factor f = DHW,S / DHW,T and then compensate for the central heating volume flow rate and thermal power on units not in DHW mode, by computing the combined volume flow (V_dotCH,DHW). In the calculation below the above example (see chapter Simultaneous flows for DHW) is used to explain how the combined volume flow rate is calculated. On the basis of the known supply temperature, flow rate and thermal power, the return temperature is calculated.
...
In the graph below, the design flow rate of DHW and CH is shown as a function of the number of apartments. The CH flow rate, logically increases linearly as the number of apartments increases (blue solid line). In the case of DHW the total flow rate DHW (green dots line) is much higher than the DHW flow rate with simultaneity (green solid line), as more apartments are added the difference increases. As explained above, because not all apartments uses DHW (simultaneity) the satellite units that are left uses CH therefore the combined flow rate is calculated (black dots line).
...
Diversity calculation methods
...
for Domestic Hot Water
...