HP & Boiler - Parallel

HP & Boiler - Parallel - HP on/off control

Working principle

The boiler and heat pump are organised as a parallel configuration. More information about the different configuration possibilities can be found in https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089204289.

The boiler is activated when the flow temperature of the system drops below 68°C, and deactivated when the flow temperature rises above 72°C. The activation also includes a check for the minimal flow rate, if the flow rate through the system is insufficient, the boiler won’t be activated. For instance, if the installation is shut down, the temperatures in the pipes will drop but the boiler won’t be activated because there is no flow through the system. During the activation of the boiler, an isolation valve at the boiler will open.

The working principle of the HP control is explained in https://hysopt.atlassian.net/wiki/spaces/HRM/pages/1247772751.

A Ground Source Heat Pump (GSHP) is used in this template, but an Air Source Heat Pump (ASHP) can also be used, this is further explained in https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089204173.

Notices/Remarks

  • The user should lock the nominal thermal power and temperatures of the HP. If not, the software will assume the propagated power and return temperature from the installation.

  • When using a thermal energy storage vessel, the user should lock the temperature regime of the heat pump. If not, the software will assume the propagated power and return temperature from the installation. The locked temperature regime is visualised in the figure below.

  • There are default COP and power tables for the heat pump, but these can be changed by the user.

  • The user can change the design temperatures, thermal power, end units, etc. Keep in mind that the controls have to be changed as well. This can be done by changing the setpoint values.

  • If the user changes the power of the end-units, the thermal capacity of the heat pump doesn’t change automatically. The user should implement a correct condenser capacity corresponded with the thermal power of the condenser. The same applies for the capacity of the boiler.

More information about the HP and boiler can be found in and .

HP & Boiler - Parallel - HP modulation

This template is a combination of the previous template “HP & Boiler - Parallel - HP on/off control” and the template .