https://www.cibse.org/knowledge/knowledge-items/detail?id=a0q3Y00000IMrmGQAT
Domestic Hot Water
Since the standard does not provide
it is not possible to define tapping points using this standard, |
With this calculation method, the diversity factor decreases according to the formula (2qm + Θ(Σqf-2qm) + Asqrt(qm*Θ)sqrt(Σqf-2qm))/Σqf, in which Σqf = T = the sum of the diversified HIU flows.
This formula only applies when 0.2 <= T. It is important to note that calculation is applicable for T expressed in liter per seconds. We assume A=3.1; Θ = 0.015; qm=0.1
No.