Application

Domestic Hot Water

This standard calculates the diversity based on

Diversity formula

With this calculation method, the diversity factor decreases according to the formula (1.19 * N + 18.8 * N^0.5 + 17.6) / (37.5*N), in which N is the number of dwellings.

The diversified flow rate for one dwelling is calculated based on the default power 37,5 kW as mentioned in the DS 439 (CIBSE CP1 2015).

Applies diversity

Requires recalculation of DHW flows?