The ‘Combined Heat and Power’ template consists of CHP combined with a storage tank and a basic control strategy.

CHP - Basic control

Working principle

The programmable controller controls the CHP. It gives the setpoint to the external PI-controller for controlling the 3-way valve to achieve a certain return temperature. Internally it will enable or disable the CHP and it will calculate the modulation based on the measured return temperature (see figure below).

The CHP is enabled on 4 conditions:

 

The CHP is disabled on 1 condition:

Controls

The following settings can be changed by the user in the programmable controller:

 

The CHP is released based on 4 conditions:

 

The modulation signal for the CHP is based on the measured temperature as follows:

Notices/Remarks

More information about the CHP can be found in ​CHP (Combined Heat & Power).