Air Source Heat Pump (ASHP) - HP stages
Working principle
The programmable controller controls the heat pump. If the top of the thermal store is below the setpoint, 40°C in this case, and the supply flow rate is higher than the minimum required flow rate, the heat pump is activated. The heat pump has in this case 2 compressors. From the moment the heat pump is activated, the first compressor will start after a certain amount of time (= stage 1). If the temperature in the top of the thermal store isn’t met yet after a certain amount of time, the second compressor will start (= stage 2). Delays are used to avoid on/off behaviour of the compressors.
Controls
The setpoint temperature can be changed with the “C” Base Circuit outside the programmable controller.
The following settings can be changed by the user in the programmable controller:
deltaT = 2;
(= hysteresis temperature, for minimal and maximal temperature before activation, or deactivation, in °C)minFlow = 0.3;
(= minimal flow rate before activation, or deactivation, in m³/h)a = SP - deltaT;
(= minimal temperature for activation, in °C)b = SP + deltaT;
(= maximal temperature for deactivation, in °C)trap1 = 0.5;
(= modulation signal in stage 1, in % )trap1 = 1;
(= modulation signal in stage 2, in % )stageOnSwitchMinutes = 10;
(= time delay before activating a new stage, in minutes )stageOffSwitchMinutes = 5;
(= time delay before deactivating a stage, in minutes )betweenStagesTimeMinutes = 10;
(= time delay between stages, in minutes )
HP1 is enabled on 3 conditions:
The top of the thermal store is below 40°C.
Temperature outside higher is than -10°C.
Timer HP1 is higher than or equal to the time delay of 4 minutes.
HP1 is disabled on 2 conditions:
Temperature outside is lower than -10°C.
The top of the thermal store is higher than 40°C.
HP2 is enabled on 3 conditions:
Heat pump 1 is working.
The top of the thermal store is below 37°C.
Timer HP2 is higher than or equal to the time delay of 4 minutes.
HP2 is disabled on 2 conditions:
Heat pump 1 isn’t working.
The top of the thermal store is higher than 40°C.
The on/off valve of HP1 is enabled on 1 condition:
Temperature outside is higher than -10°C.
The on/off valve of HP1 is disabled on 1 condition:
Temperature outside is lower than -10°C.
The on/off valve of HP2 is enabled on 2 conditions:
The top of the thermal store is lower than 37°C.
On/off valve of HP1 is open.
The on/off valve of HP2 is disabled on 2 conditions:
The top of the thermal store is higher than 40°C.
On/off valve of HP1 is closed.
Notices/Remarks
The system can be further optimised by doing sensitivity studies. For instance, a sensitivity study can be done for the size of the storage vessel.
The user can change the design temperatures, thermal power, end units, etc. Keep in mind that the controls have to be changed as well. This can be done by changing the “settings” in the programmable controller which are listed in the top of the code. After changing the settings, the correct operation has to be checked again. The user should only change the “settings” and nothing else in the code to make sure the correct control strategy is still valid.
If the user changes the power of the end-units the thermal capacity of the condenser doesn’t change automatically. The user should implement a correct capacity corresponded with the thermal power of the heat pump.
This template was developed with an air source heat pump. To use a ground source heat pump you need to apply the following modification:
Change the external temperature by a sine wave to the evaporation temperature of the heat pump
More information about the HP can be found in Heat pump.