The heat pump for heating and cooling is similar to the booster, but instead of supplying heat on the evaporator side, cooling is produced to be used in the system.

Most of the parameterisation is similar to the standard https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089204173/Heat+pump, however, some more evaporator components are added, which can be filled in the same way as the condenser side. Make sure to fill in the evaporator capacity and KV value.

...

Info

The design power of the BC for the heat pump for heating and cooling relates to the heating design power. The design power of the evaporator is derived from the design heating power, the COP table and the electrical power table. For design conditions: e.g. 90 kW condenser power (W15/W45) has a prescribed COP of 6 in the datasheet for full load at those temperature conditions. The design cooling power can then be calculated:

...