Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Before doing any calculations (see actions button), the software will always first verify whether the model is consistent to proceed further calculations. When information is missing or information is not consistent, the model cannot be validated and the software will indicate the inconsistency or error.

Image RemovedImage Added

Model inconsistencies and errors might be be indicated on nodes as well as on basic circuits. When a model inconsistency is indicated on a node, the respective node is marked with an orange circle.

...

The figures below illustrate some typical examples of model errors.

 

Image RemovedImage Added

'Dead end node' means that this model is not complete. This pipe segment needs to be connected with a basic circuit.


Image RemovedImage RemovedImage AddedImage Added

The basic circuit of the pump indicates there is a warning called 'Pumps found downstream of this pump'. Which means that ther're several pumps in series.

The color of the active mixing basic circuit indicates there is an error called 'Pump in variable part of mixing ciruit'. For the proper operation of the active mixing circuit, a primary pump should not be placed before mixing circuit..

Image RemovedImage Added

This basic circuit indicates that this 'base circuit is reversed' which means that the entry and exit of the base circuit is installed in the opposite way.