ILS error codes

If one of the following errors occur on an ILS base circuit, a comfort issue is applicable. It actually means that one of the assumptions made by the ILS algorithm (see Real Time Simulation (RTS) versus Imposed Load Simulation (ILS) ) could not be realized for more than 5% of the time, implying some kind of comfort issue.

The ILS simulation result is INVALID because of that reason not reliable.
You will need to fix the comfort issue in order to create a valid and reliable simulation result!

  • error code 2
    cause : the imposed volume flow for heating for an individual dwelling was larger than the design flow
    this can occur if e.g. the supply temperature is too low, if the room setpoint temperature is higher than room design temperature (20), or if the outside temperature is lower than -10.
    solution : adapt the supply temperature, the room setpoint temperature, or modify your design conditions

  • error code 4
    cause : the imposed volume flow for heating, secondary from the heat exchanger, for an individual dwelling was larger than the design flow. This can occur if e.g. the controlled radiator supply temperature is too low, if the room setpoint temperature is higher than room design temperature (20), or if the outside temperature is lower than -10.
    solution : adapt the supply temperature, the controlled radiator supply temperature , the room setpoint temperature, or modify your design conditions

  • error code 8
    cause : the central heating setpoint configuration does not comply with the central heating diversity standard as defined in the settings page. The peak flows exceeded the flows as defined by the diversity standard.
    solution:

    • Either change the diversity standard in the settings page

    • either change the setpoint configuration (simulation parameter)

  • error code 16
    cause : the imposed volume flow for Domestic Hot Water for an individual dwelling was larger than the design flow, this can occur if e.g. the supply temperature is too low
    solution : adapt the supply temperature or the domestic hot water temperature

  • error code 32
    cause : the room temperature could not be realised. This can occur if e.g. the supply temperature or controlled radiator supply temperature is too low, room setpoint temperature is higher than room design temperature (20) or the outside temperature is lower than -10
    solution : adapt the supply temperature, the controlled radiator supply temperature , the room setpoint temperature, or modify your design conditions

  • error code 64
    cause : the primary supply temperature is lower than the secondary controlled radiator supply temperature
    solution : adapt the supply temperature or the controlled radiator supply temperature
    IF THIS IS THE ONLY ERROR YOU HAVE ON YOUR ILS BLOCK, THAN YOU CAN IGNORE THIS, BECAUSE IT DOES NOT LEAD TO A COMFORT ISSUE

  • error code 128
    cause : the supply temperature is lower than the Domestic Hot Water temperature
    solution : adapt the supply temperature or the Domestic Hot Water temperature

...

As an example, here you can see the resulting return temperature of an ILS simulation.
There are two spikes which seem odd and cannot be explained.

...

By overlaying the stepsizes on which an ILS error code occuredselecting the “ILS error code(s)”, the graph shows the moments when an error occurs.

...

You can see that the spikes occured occurred on a timestep that an ILS error occuredoccurred, making the return temperatures on these two time steps invalid.

...