The BTES 1.4 Base Circuit is based on the hydraulic configuration of a concept commonly used in Belgium.
...
Since a heat exchanger is used, this is a closed system.
...
Operating conditions
The BTES 1.4 BC has different operating conditions. There are two suggested operating conditions the BC should operate in: Cold withdraw and Cold deposit.
Cold withdraw
...
In the operating condition “cold withdraw”, the coolth cold stored in the ground is used to cool down the building, meanwhile heating up the fluid and the heat stored in the ground.
Cold deposit
...
In the operating condition “cold deposit”, the
In other words, during cold withdraw, cold stored in the ground is delivered to the building to perform cooling. The warm return is pumped back into the ground, therefore heating up the fluid in the ground and increasing the amount of heat stored in the ground (reducing the amount of cold, therefore, soil temperature goes up). This condition is used to heat up the building (commonly done by a heat pump), meanwhile cooling down the fluid and the cooled stored in the ground.mostly used in summer.
Cold deposit
...
During cold deposit, the heat pump (or different source) is delivering heat to the building, the rest cold of the heat pump is then stored into the ground, which lowers the soil temperature. This condition is mostly used in winter.
Design
The BTES system has two design conditions, one for summer “Cold withdraw” and one for winter “Cold deposit”. All the components inside the BC and on the primary side of the BC are active in both design conditions. The design of every component is clarified by going through the design flow for both full load conditions.
...
The design flow rates are separately calculated for “Cold withdraw” and “Cold deposit”. All the temperatures and thermal powers are needed. To clarify the design conditions, the user can toggle the hotkey “Ctrl+O”, which shows the two full load design conditions. “Cold withdraw” is visualised in the figure on the left and “Cold deposit” in the figure on the right.
...
Cold withdraw
In the figure below the required input data is visualised to calculate the volume flow rate for “Cold withdraw”.
...
In the figure below the KV-value and the UA-value of the borehole heat exchanger are shown. The KV-value is needed for the pressure drop calculation.
...
The UA - value is separately calculated for “Cold withdraw” and “Cold deposit”. The largest UA-value is taken as the actual value, except if the user overrides the UA - value by locking it. This is done to get a UA-value that is usable for both “Cold withdraw” and “Cold deposit”.
If for instance the UA value for “Cold withdraw” is larger than “Cold deposit”, the implemented temperatures for “Cold deposit” aren’t correct anymorewill no longer be valid, as they are depended on the UA-value. With that in mind, the design temperature of the soil is recalculated. This example is given in the figure below, where the UA-value is calculated for cold withdraw mode, therefore the soil temperature in cold deposit is recalculated.
...
In the figure above the flow rate of “Cold deposit” is larger than the flow rate of “Cold withdraw” which means the flow rate of “Cold deposit” is propagated to the production side. However the UA-value of “Cold withdraw” is larger, which means the design temperature of the soil for “Cold deposit” changed.
...
A warning is also shown during a “system check” if a pump is placed on the primary side because two pumps are in series, which is suboptimal in most cases. More info on pumps can be found in Pumps https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089205023.
...
Simulation
In a simulation, controls are needed to make sure the BTES BC does what the user wants it to do. To control the BC correctly, different enable signals (green) and measuring signals (red) are implemented in the BC.
...
Pump modulation signal
If a signal between 0 and 1 is sent to this node, the pump will modulate between 100% rpm and its minimum modulation (in default 10%). This is only the case if the pump is activated.Pump activation signal
If a signal 1 is sent to this node, the pump is activated. If a signal 0 is send the pump is deactivated and won't generate any flow.Borehole temperature production side
Soil temperature
Borehole temperature end-unit side
Simulation parameters
Furthermore, there are still a few setting the user can change for simulation. To change these settings, the user should activate the simulation layer on the right side of the library.
...
After the activation, the user can see a couple more parameters, visualised in the figure below. The minimal pump head percentage and change speed are not discussed in this page because these are specific parameters for the pump itself, which is the same as in other BC’s. More info on pumps can be found in Pumps https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089205023.
...
The natural soil temperature is necessary to simulate the thermal losses of the stored heat or coolth compared to the natural soil surrounding the stored energy. The default value of the natural soil temperature is 12°C.
...
The simulation mode “Sine wave” means the temperatures in the soil doesn’t change depending on the injected or extracted energy. The temperatures are exactly the same as the set sine waves by the user. If this simulation mode is selected, the thermal imbalance of the soil won’t be visual by the temperatures of the soil. The pop-up window of the simulation mode “Sine wave” is shown in the figure below.
...
The thermal loss coefficient is the same as in the “Capacity mode”. The thermal loss, however, doesn’t have any impact on the temperature variation of the soil.
To set the sine wave for the soil, the user should insert the maximum and minimum temperature. The sine wave is set up in such a way that the minimum value is reached after the peak winter days and the maximum value is reached after the peak summer days (of an average year). The clarification is visualised in the figure below.
...
Load matching BTES
The BTES system can be load matched with measured data when it is available. When the building owner is interested in installing a BTES system, sometimes a TRT (Thermal Response Test) is used to check the application of a BTES system. This TRT can also be used to load match the BTES BC for an accurate simulation.
...
This principle can be implemented and simulated in the Hysopt software. The template for it is clarified in BTES load matching https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089370999 and can be found in our Hysopt Inspiration Library (Hysopt Inspiration Libraryhttps://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089368971/Inspiration+Library+-+Templates ). The template is visualised in the image below.
...
This trend function can be imported in the software using a .csv file. When doing so, the template can be used to change the thermal loss coefficient and capacity to load match the BTES system. The image below shows the simulation data (green) and the trend date imported in the software (purple).
...
However, the load matching is only done for 1 probe. So when the user has multiple probes, the parameters should be scaled in a correct way. The correct way to scale them is explained in BTES load matching https://hysopt.atlassian.net/wiki/spaces/HRM/pages/3089370999.