Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Individual components and parameters

  1. 2-way valve
  2. Balance valve for primary balancing
  3. Differential pressure control valve

...


When the DPCV is applied across a balance valve (BV), the flow through the balance valve remains constant even if the pressure difference across the BV-DPCV combination changes. This might be useful in specfic situations in which the hydraulic system balance must be assured in partial load working conditions.                         


If the differential pressure across a control valve is maintained constant by means of a DPCV, the control valves authority is theoretically 1 and completely insensitive to hydraulic interactivity. This way the control performance
of the respective control loop might be increased. 

...