Error message

Translation of the error

solution

The value of ‘Heat flow on primary circuit’ is higher than the heat flow that is needed behind the base circuit.

Lower the value of 'Heat flow on primary circuit' until it is below the needed heat flow behind the base circuit.

The Hysopt software calculates everything from the end units to production units and this message says that it could not do his calculations for the last 6 nodes.

Hover with your mouse over the red node/base circuit closest to the end units to get additional information about the error.

The ‘Heat flow on primary circuit’ is the same as the heat flow that is needed behind the base circuit

Lower the value of ‘Heat flow on primary circuit' until it is below the needed heat flow behind the base circuit

The ‘Primary power percentage’ is set on 100%

Lower the percentage in 'Primary power percentage’

Switched production

Base circuit and parameters

Switched parallel production makes it possible to configure multiple productions that work individually in one system. The following figure shows on the left the base circuit of switched production and on the right the parameter window that pops up when you click on the base circuit. The numbers on the base circuit indicate which gate is the primary and secondary gate. This base circuit is used when you have a production unit that is only used when the other one is no longer sufficient. For example, a backup boiler that is used when the heat pump is no longer sufficient.

...