Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The templates consists of various configurations of a biomass boiler combined with a gas boiler.

Biomass boiler & Gas boiler - Parallel

...

Working principle

The programmable controller controls the biomass boiler, visualised in the figure below. It gives the setpoint to the external PI-controller for regulating the 3-way valve on the setpoint return temperature. Internally it will enable or disable the biomass boiler and it will calculate the modulation based on the measured return temperature.

...

The gas boiler is activated when the flow temperature of the system drops under 73°C, and deactivated when the flow temperature rises over 77°C. The activation also includes a check for the minimal flow rate, if the flow rate through the system is insufficient, the boiler won’t be activated. For instance, if the installation is shut down, the temperatures in the pipes will drop but the gas boiler won’t be activated because there is no flow through the system. During the activation of the gas boiler, an isolation valve at the boiler will open.

...

Controls

More information about the controls of the biomass boiler can be found in Biomass boiler.

Notices/Remarks

  • The system can be further optimised by doing sensitivity studies. For instance, a sensitivity study can be done for the size of the storage vessel or the thermal power of the biomass boiler. To change the thermal power, the user should change the power spread found in the hybrid production configuration BC. More information about hybrid production configurations can be found in Hybrid production Heating.

...

More information about the CHP and boiler can be found in Biomass boiler and Condensing boiler.

Biomass boiler & Gas boiler - Reverse shunt in return

...

Idem as the template “Biomass boiler & Gas boiler - Parallel”, except for the shunt configuration instead of the parallel configuration. There is also a bypass valve to bypass the gas boiler when the gas boiler is deactivated.

More information about hybrid production configurations can be found in Hybrid production Heating.

Biomass boiler & Gas boiler - Reverse shunt in supply

...

Idem as the template “Biomass boiler & Gas boiler - Parallel”, except for the shunt configuration instead of the parallel configuration.

More information about hybrid production configurations can be found in Hybrid production Heating.

Biomass boiler & Gas boiler - Switchable serial in supply

...

Idem as the template “Biomass boiler & Gas boiler - Parallel”, except for the serial configuration instead of the parallel configuration. There is also a bypass valve to bypass the gas boiler when the gas boiler is deactivated.

...