More information on pumps can be found in Pumps.

Pump control - Temperature control over

...

low loss header - 2 points

...

The rpm of the pump is modulated to minimise the overflow from hot water generated from the boiler into the return pipe. A high return temperature can result in lower production efficiency. By modulating the pump to maintain a certain temperature difference before and after the low loss header, the overflow is minimised. In this case, the supply temperature is measured and used. More information on the disadvantages of a low loss header can be found in Header configuration.

Pump control - Temperature control over

...

low loss header - 4 points

...

This template is similar to the previous template “Pump control - Temperature control over open low loss header - 2 points“, except for the use of four temperatures instead of two. In this case both the flow temperatures as the return temperatures are used to modulate the pump rpm.

...