Thermal balance soil
The soil temperature without an ATES or BTES system would be almost constant throughout the year. If an ATES or BTES system is used, and we start in January, the temperature of the soil would gradually drop in the winter months because heat is extracted from the soil (= injecting cold). In the summer months, the soil temperature will gradually rise because the cold is extracted from the soil to cool down the building. After the summer, the winter comes again, meaning the temperature will drop again. This is visualised in the figure below.
...
If the same amount of cold is extracted from the soil, as there is injected, the temperature at the end of the year would be exactly the same as in the beginning. This is called a thermally balanced soil.
However, if more cold is injected than there is extracted, the temperature would gradually drop every year. This is visualised in the graph below which shows the soil temperature in a 3-year simulation. In this case, the BTES is after a few years too cold.
...
The same thing can be said if the extracted cold is larger than the injected cold. The temperature will gradually rise every year.
...
A thermal imbalance of the soil reduces the system efficiency of the system because of the increasing thermal losses in the soil and the lowered SCOP value of the heat pump. It can even lead to a thermal breakdown of the system, meaning no cold can be injected or extracted anymore.
For this reason, more options are available in the template to give the user some strategies to make sure the thermal balance is met with an optimal system efficiency.