Measured return temperature is lower than maximum return temperature.
Once the biomass boiler has been disabled the sequence to enable the biomass boiler shall be inhibited for 10 minutes -> check of this timer has run out.
Number of starts within 24h is lower than 6.
Temperature in TES is lower than 70°C.
The
The biomass boiler is disabled on 1 condition:
...
When using a thermal energy storage vessel, the user should lock the temperature regime of the biomass boiler, or else the software will calculate with the propagated power and return temperature from the installation. The locked temperature regime is visualised in the figure below.
...